Product Details:
Payment & Shipping Terms:
|
Rated Voltage: | 220V - 240V | Rated Current: | 0 . 19A |
---|---|---|---|
Speed: | 1300RPM | Frequency: | 50/60Hz |
Material: | Frame: Cast Iron, Impeller: Aluminum Alloy | Weight: | 820g |
High Light: | electronic equipment cooling fans,industrial roof ventilation fans |
AC Tangential Blower Industrial Ventilation Fans 420mm 230 Volt
Application:
This blower are commonly used in HVAC systems,machinery for heating, ventilating, air conditioning, drying, dehumidifying, etc. Such as electronic air cleaner , hand dryers,electronic oven, gas oven, electronic fireplace, gas fireplace, electric fan good balance condition,etc.
ELECTRICAL CHARACTERISTICS:
ALL MEASUREMENTS PERFORMED AT25~30℃ ROOM TEMPERATURE
& 50~80%R.H.UNLESS OTHERWISE SECIFIED.
1 |
RATED VOLTAGE |
VOLTS |
V |
220 VAC |
|
2 |
OPERATION VOLTAGE |
VOLTS |
V |
160-242 |
|
3 |
FREQUENCY |
Hz |
Hz |
50 |
|
4 |
INPUT CURREN |
AMP |
A |
0.19A±10% |
AT RATED VOLTAGE |
5 |
INPUT POWER |
WATTS |
W |
25W ±10% |
AT RATED VOLTAGE |
6 |
ROTATION SPEED |
RPM |
RPM |
1300±10% |
|
7 |
ACOUSTICAL NOISE(AVG) |
dB(A) |
dB(A) |
≤48 |
DETAILS SEE ATTACHED PAGE. |
8 |
MAX .AIR-FLOW |
CFM |
Q |
89 |
TWO-CHAMBER METHODS DEAILS SEE ATTACHED PAGE. |
9 |
MAX . AIR-PRESSURE |
mmAq |
P |
2.2 |
TWO-CHAMBER METHODS DEAILS SEE ATTACHED PAGE. |
10 |
INSULATION RESISTANCE |
MEG. OHM |
MΩ |
>20 MΩ |
BETWEEN FRAME AND TERMINAL |
11 |
DIELECTRIC STRENGTH |
|
|
1800V,3S,1MA |
BETWEEN FRAME AND TERMINAL. |
12 |
ROTARY DIRECTION |
|
|
CC W |
|
13 |
INSULATION CLASS |
|
|
CLASS E |
|
14 |
LIFE EXPECTANCY |
|
|
15000 Hours at 25℃/65%RH |
|
Dimensions (Unit:mm)
Specification :
Description :
ENVIRONMENTAL:
1.OPERATING TEMPERATURE----------------------- -20 TO+50℃(CLASS E)
2.STORAGE TEMPERATURE ------------------------- -30 TO+75℃
3.OPERATING HOMIDITY-----------------------------------RH20%-80%
Product Picture:
How to Select a right cooling fan?
A: Where are you used? Application for what?
B: What's size limitation do you have?
C: What's voltage do you require (5V DC,12/24V DC, 85V-125V ,190V-250V)?
D: What's power or CFM airflow required?